The Shinko DCL-33A is a compact DIN rail-mounted temperature and process controller designed for industrial applications. Below are its key specifications:

Here are the key specifications for the Shinko DCL-33A DIN rail-mounted indicating controller:
📏 Physical Dimensions
- Width: 22.5 mm
- Height: 75 mm
- Depth: 100 mm
⚡ Power Supply Options
- 100 to 240 V AC (standard)
- 24 V AC/DC (optional; ensure correct polarity for DC)
🔌 Input Types (Multi-Input Capability)
- Thermocouples: K, J, R, S, B, E, T, N, PLII, WRe5-26
- RTDs: Pt100, JPt100
- DC Current: 4–20 mA DC, 0–20 mA DC (with built-in 50 Ω shunt resistor)
- DC Voltage: 0–1 V, 0–5 V, 1–5 V, 0–10 V
🌡️ Measurement Range
- Thermocouple K: –200 to 1370°C (–320 to 2500°F)
- Thermocouple J: –199.9 to 400.0°C (–199.9 to 750.0°F)
- Thermocouple R/S: 0 to 1760°C (0 to 3200°F)
- DC Inputs: –1999 to 9999 (configurable with decimal point selection)
🔧 Control Outputs
- OUT1: Primary control output (relay, voltage pulse, or current)
- OUT2: Heating/Cooling control output (DC option)
🔔 Alarm and Event Outputs
- Alarm Output: Standard single alarm output
- Event Output: Outputs when alarm, loop break alarm, or heater burnout alarm is ON
🔄 Control Functions
- Control Action: PID or ON/OFF
- Proportional Band: 0.0 to 10.0 times OUT1 proportional band
- Integral Time: Same as OUT1
- Derivative Time: Same as OUT1
- Proportional Cycle: 1 to 120 seconds
- Overlap/Dead Band:
- Thermocouple/RTD Input: –100.0 to 100.0
- DC Voltage/Current Input: –1000 to 1000 (decimal point placement follows selection)
📡 Communication
- Serial Communication: EIA RS-485 (C5 option)
- Protocol: Modbus (optional)
🔍 Display
- PV (Process Value): Red, 4 digits, 7.5 x 4.1 mm (H x W)
- SV (Set Value): Green, 4 digits, 7.5 x 4.1 mm (H x W)
✅ Certifications
- UL
- CUL
- CE
🧩 Additional Features
- Heater Burnout Alarm Output: Available in 5A, 10A, 20A, and 50A options
- External Setting Input: EA option
- Set Value Memory External Selection: EI option
For detailed information on wiring, configuration, and operation, please refer to the official Shinko DCL-33A manual that we can supply you.