BCS2 Digital Indicating Controller NEW
-Convenient Initial setting mode
-AT on startup function
-Simplified Program control
-Simplified converter function
-A variety of Event Input/Output functions
-Large, easy-to-view, 5-digit PV, SV Displays
-Compact, 60 mm-deep control panel interior
-Simple settings from a PC
-Drip-proof/Dust-proof IP66
*New Standard Controllers*
|
|
BCx2 series, Shinko's digital indicating controllers are succession models of the JC series, with remarkable enhancement in operation, control performance, function, visibility, and compactness, etc.
|
|
Convenient Initial setting mode! |
|
|
|
AT on startup function! |
|
This function can be used when usual AT cannot be performed normally due to temperature fluctuations. PID parameters can be calculated only when the temperature is rising.
'AT on startup' action
|
|
|
(1) Calculating AT (from startup, until PV is stabilized at SV)
(2) PID constants calculated
(3) Controls with PID constants set by the 'AT on startup'. |
|
Simplified Program control! |
|
The 9-step pattern is a standard feature.
Time signal output and Pattern end output can be selected in [Event output allocation].
-Number of patterns: 1
-Number of steps: 9
-Step SV: Scaling low limit value to Scaling high limit value
-Step time: 00:00 to 99:59 (Unit: Hours:Minutes, Minutes:Seconds)
-Wait value: 0 to Converted value of 20% of input span (or scaling span)
-Power restore action: Stop/Continue/Suspend (on hold)
-Program control start type: PV start/PVR start/SV start
-Number of repetitions: 0 to 10,000
Program pattern example
|
|
|
Simplified converter function! |
|
For DC current output type, the controller can be used as a converter.
Input signal is converted to insulated 4 to 20 mA DC, and outputted at the converted value. |
|
A variety of Event Input/Output functions! |
|
A maximum of 2 points of Event input (optional), and 2 points of Event output (1 point is standard).
Selectable from various Input/Output choices: Alarm output, Heater burnout alarm output (optional), Loop break alarm output, Time signal output, Pattern end output, etc. |
TOP
|
Large, Easy-to-view, 5-digit PV, SV Displays! |
|
Large, easy-to-view, 5-digit PV, SV Displays, useful for indicating a wide range of measurement ranges.
-BCD2: Character size 24 x 11 mm (H x W)
-JCD-33A: Character size 18 x 8 mm (H x W)
BCD2
JCD-33A
|
|
Compact, 60 mm-deep control panel interior! |
|
With a depth of only 60 mm, the BCx2 series is ideal for mounting in nearly any control panel situation.
-BCD2: Depth of control panel interior 60 mm
-JCD-33A: Needs a control panel interior of 98.5 mm
Comparing BCD2 and JCD-33A
|
?? |
Simple settings from a PC |
|
By connecting the BCx2 to a PC using the tool cable (sold separately), and by using dedicated software, various settings can be carried out. Wiring of BCx2 is not necessary as power to the BCx2 is supplied by PC via USB.
Dedicated software can be downloaded from Shinko website (Support & Downloads)
BCx2 series console software (SWC-BCx01M)
|
|
|
Model |
|
(*1): |
Thermocouple, RTD, Direct current or DC voltage are selectable by keypad. |
(*2): |
Only one option can be selected from Option 1 and Option 2 respectively. |
(*3): |
Event output EV1 is standard.
The following outputs can be selected in [Event output EV1/EV2 allocation] by keypad:
Alarm output (12 alarm types and No alarm action), Heater burnout alarm output, Loop break alarm output, Time signal output, Output during AT, Pattern end output, Output by communication command, Heating/Cooling control output OUT2 (for EV2 option only)
For Event output EV1/EV2, Heater burnout alarm output and Output by communication command are available when C5W, EIW, C5 or W option is ordered. |
(*4): |
For the BCS2, 2 points of Event input are not available. |
(*5): |
For Direct current output type, Heater burnout alarm does not work. CT is sold separately. |
(*6): |
For the BCS2, 1 point of Event input is available. |
|
|
|
Drip-proof/Dust-proof IP 66 |
|
IP66 structure (for the front panel) allows usage in harsh environments where the controller is exposed to water or dust. |
|
|
Rating |
|
Rated scale |
|
Input |
Thermocouple |
K, J, R, S, B, E, T, N, PL-II, C(W/Re5-26)
External resistance: 100 max.
However, for B input, External resistance: 40 max. |
RTD |
Pt100, JPt100 3-wire type
Allowable input lead wire resistance: 10 max. per wire |
Direct current |
0 to 20 mA DC, 4 to 20 mA DC
Input impedance: 50 max.
Allowable input current: 50 mA max. |
DC voltage |
0 to 1 V DC
Input impedance: 1 M min.
Allowable input voltage: 5 V DC max.
Allowable signal source resistance: 2 k max. |
0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
Input impedance: 100 k min.
Allowable input voltage: 15 V DC max.
Allowable signal source resistance: 100 max. |
|
Power supply voltage |
100 to 240 V AC 50/60 Hz, 24 V AC/DC 50/60 Hz |
Allowable voltage fluctuation |
85 to 264 V AC, 20 to 28 V AC/DC |
|
|
|
General Structure |
|
External
dimensions |
BCS2 |
48 x 48 x 68 mm (W x H x D) (60 mm-deep control panel interior) |
BCR2 |
48 x 96 x 68 mm (W x H x D) (60 mm-deep control panel interior) |
BCD2 |
96 x 96 x 68 mm (W x H x D) (60 mm-deep control panel interior) |
|
Mounting |
Flush |
Case |
Flame-resistant resin, Black |
Front panel |
Membrane sheet |
Drip-proof/
Dust-proof |
Front panel: IP66, Rear case: IP20, Terminal section: IP00 |
Display |
BCS2 |
PV Display: 12.4 x 5.8 mm (H x W)
SV Display: 8.8 x 3.9 mm (H x W) |
BCR2 |
PV Display: 14 x 5.8 mm (H x W)
SV Display: 14 x 5.8 mm (H x W)
STEP/MEMO Display: 14 x 5.8 mm (H x W) |
BCD2 |
PV Display: 24 x 11 mm (H x W)
SV Display: 14 x 7 mm (H x W)
STEP/MEMO Display: 14 x 7 mm (H x W) |
|
|
|
TOP
|
Indication Performance |
|
Basic accuracy |
At ambient temperature 23 (for a single unit mounting)
|
Effect of ambient temperature |
Within 50 ppm/ of each input span |
Input sampling period |
125 ms |
Time accuracy |
Within 1.0% of setting time |
|
|
|
Control Performance |
|
Control action |
PID control (with AT function)
PI control: When derivative time is set to 0
PD control (with auto-reset, Manual reset function): When integral time is set to 0
P control (with auto-reset, Manual reset function): When derivative and integral times are set to 0.
ON/OFF control: When proportional band is set to 0 (or 0.0)
Proportional band (P) |
0 to Input span ()
Direct current, voltage inputs: 0.0 to 1000.0% |
Integral time (I) |
0 to 3600 sec |
Derivative time (D) |
0 to 1800 sec |
Proportional cycle |
0.5, or 1 to 120 sec |
ARW |
0 to 100% |
Manual reset |
Proportional band value |
ON/OFF hysteresis |
0.1 to 1000.0 ()
Direct current, voltage inputs: 1 to 10000 |
OUT1 high limit,
OUT1 low limit |
0 to 100 %
Direct current output: -5 to 105% |
|
Control
output |
Relay contact 1a |
Control capacity: 3 A 250 V AC(resistive load),
1 A 250 V AC(inductive load cos=0.4)
Electrical life: 100,000 cycles
Minimum applicable load: 10 mA 5 V DC |
Non-contact voltage
(for SSR drive) |
12 V DC15 %
Max. 40 mA(short circuit protected) |
Direct current |
4 to 20 mA DC
Load resistance: Max. 550 |
|
|
|
|
Standard Functions |
|
EV1 output |
The output is turned ON or OFF depending on the conditions selected in [Event output EV1 allocation]. |
Simplified converter
function |
This instrument can be used as a converter for Direct current output type.
Input signal is converted to insulated 4 to 20 mA, and outputted. |
Attached function |
Sensor correction coefficient, Sensor correction, Set value lock, Auto/Manual control, SV ramp, SV Rise/Fall rate start type, Program control, Power failure countermeasure, Self diagnosis, Automatic cold junction temperature compensation, Input error, Burnout, Warm-up indication |
|
|
TOP
|
Optional Functions |
|
Event input
BCS2 (EIW, EIT, EI options)
BCR2/BCD2 (C5W, EIW, EIT, EI options) |
2 points of Event input (1 point for EIT option for the BCS2) can be applied.
Events selected in [Event input DI1/DI2 allocation] will be performed depending on the DI1/DI2 input ON (Closed) or OFF (Open) status.
Circuit current when Closed: Approx. 16 mA
|
Event output
(EV2 option) |
Output will be turned ON or OFF depending on the event conditions selected in [Event output EV2 allocation].
Relay contact 1a
|
Heater burnout alarm
(C5W, EIW, W options) |
Monitors heater current with CT (current transformer), and detects burnout.
EV1/EV2 output, for which Heater burnout alarm is selected in [Event output EV1/EV2 allocation], will be turned ON or OFF.
This alarm is also activated when indication is burnout.
Rated current |
20 A, 100 A (Must be specified when ordering.)
Single-phase: Detects burnout with CT1 input.
3-phase: Detects burnout with CT1 and CT2 inputs. |
Setting accuracy |
5% of the rated value |
|
Heating/Cooling control
(DS, DA, EV2 options) |
Performs Heating/Cooling control.
One cooling method can be selected via keypad.
-Air cooling (linear characteristics)
-Oil cooling (1.5th power of the linear characteristics)
-Water cooling (2nd power of the linear characteristics)
OUT2
-DS: Non-contact voltage (for SSR drive)
-DA: Direct current
-EV2: Relay contact 1a |
Serial communication
(C5W, C5 options) |
The following operations can be carried out from an external computer.
(1) Reading and setting of the SV, PID values and various set values
(2) Reading of the PV and action status
(3) Function change
Communication line |
EIA RS-485 |
Communication method |
Half-duplex communication |
Communication speed |
9600, 19200, 38400bps (Selectable by keypad) |
Synchronization method |
Start-stop synchronization |
Data bit/Parity |
7 bits, 8 bits/Even, Odd, No parity (Selectable by keypad) |
Stop bit |
1 bit, 2 bits (Selectable by keypad) |
Communication protocol |
Shinko protocol, Modbus ASCII, Modbus RTU (Selectable by keypad) |
Digital external setting:
Receives digital set values from Shinko programmable controllers
(PC-900, PCD-33A with SVTC option). |
External setting input
(EIT option) |
SV adds external analog signal to remote bias value.
Not available for Program control.
Setting signal |
4 to 20 mA DC |
Allowable input |
50 mA DC max. |
Input impedance |
50 max. |
Input sampling period |
125 ms |
|
Transmission output
(EIT option) |
Converting the value (PV, SV, MV or DV transmission) to analog signal every 125 ms, outputs the value in current or voltage. Outputs Transmission output low limit value if Transmission output high limit and low limit values are the same.
Resolution |
12000 |
Output |
4 to 20 mA DC (Load resistance: Maximum 550 ) |
Output accuracy |
Within 0.3% of Transmission output span |
|
Insulated power output
(P24 option) |
Output voltage |
24 V3 V DC (when load current is 30 mA DC) |
Ripple voltage |
Within 200 mV DC (when load current is 30 mA DC) |
Max. load current |
30 mA DC |
|
|
|
|
Insulation, Dielectric Strength |
|
Insulation resistance |
10 M minimum, at 500 V DC
When OUT1 and OUT2 are a non-contact voltage output or Direct current output, OUT1 is not electrically insulated from OUT2. |
Dielectric strength |
Between input terminal and power terminal: 1.5 kV AC for 1 minute
Between output terminal and power terminal: 1.5 kV AC for 1 minute
Between output terminal(P24) and power terminal: 500 V AC for 1 minute |
|
|
|
Other |
|
Power consumption |
100 to 240 V AC |
Approx. 8 VA max.(When a maximum of options are added: Approx. 11 VA max.) |
24 V AC |
Approx. 5 VA max.(When a maximum of options are added: Approx. 8 VA max.) |
24 V DC |
Approx. 5 W max.(When a maximum of options are added: Approx. 8 W max.) |
|
Ambient temperature |
-10 to 55 (Non-condensing, No icing) |
Ambient humidity |
35 to 85%RH (Non-condensing) |
Weight |
BCS2 |
Approx. 110 g |
BCR2 |
Approx. 160 g |
BCD2 |
Approx. 220 g |
|
|
|
|
Terminal arrangement |
|
BCS2
BCR2, BCD2
|
|
|
External dimensions (Scale: mm) |
|
BCS2
|
|
(*) When the terminal cover is used. |
|
|